The RM-DPT devices from the SensorLine range are differential pressure transmitters for application in harsh industrial environments. They are used to measure non-corrosive gaseous media in above atmospheric and negative pressure ranges.
The transmitters convert the mechanical quantity pressure/differential pressure to an electrical measuring signal. Within the calibrated measuring range, the electrical output signal is proportional to the applied pressure/differential pressure. Thanks to the use of piezoresistive measuring cells and highly precise compensation and evaluation electronics the transmitters are calibrated for a broad temperature range with very narrow error margins.
Devices with different measuring ranges and accuracy classes in 2-wire or 4-wire connection are available to cover a wide range of applications. Two-wire connected transmitters are also available as twin transmitters in a single box. All box-type versions are also available for Ex areas acc. to ATEX zone 22, cat. 3D. The explosion proof versions are approved by DEKRA-EXAM.
For RECO control systems and automation devices, the transmitters are also available as snap-on modules.
| System | Laser-trimmed piezoresistive measuring bridge |
|---|---|
| Tests |
Box from polycarbonate in RAL 7035, IP 66 / NEMA 4 / IK08 |
| Box from polycarbonate in RAL 5015, IP66 / NEMA 4 / IK08, ATEX Zone 22, BVS 03 E 141 | |
| Norms / Conformity | IEC 770, EN 50081-1, EN 61000-6-2, 2004/108/EC |
| Technical specifications Sensor (Part 1) |
RM-DPT 504 RM-DPT 504 ATEX |
RM-DPT 1002 RM-DPT 1002 ATEX RM-DPT 1004 RM-DPT 1004 ATEX |
RM-DPT 2002 RM-DPT 2002 ATEX RM-DPT 2002 2002 RM-DPT 2002 2002 ATEX RM-DPT 2004 RM-DPT 2004 ATEX |
|---|---|---|---|
| Measuring range | 0 ... 500 Pa | 0 ... 1000 Pa | 0 ... 2000 Pa |
| Output signal corresponds to measuring limit |
4-20 mA ≙ 0 ... 500 Pa |
4-20 mA ≙ 0 ... 1000 Pa |
4-20 mA ≙ 0 ... 2000 Pa |
| Full scale output (FSO) | 500 Pa | 1000 Pa | 2000 Pa |
| Accuracy (linearity and hysteresis) |
≤ ± 1 %FSO ≙ ≤ ± 5 Pa |
≤ ± 1 %FSO ≙ ≤ ± 10 Pa |
≤ ± 1 %FSO ≙ ≤ ± 20 Pa |
| One-side overpressure safety | 20 kPa | 70 kPa | 70 kPa |
| Technical specifications Sensor (Part 2) |
RM-DPT 4002 RM-DPT 4002 ATEX RM-DPT 4002 4002 RM-DPT 4002 4002 ATEX RM-DPT 4004 RM-DPT 4004 ATEX |
RM-DPT 5002 RM-DPT 5002 ATEX RM-DPT 5002 5002 RM-DPT 5002 5002 ATEXRM-DPT 5004 RM-DPT 5004 ATEX |
RM-DPT 10002 RM-DPT 10002 ATEX RM-DPT 10004 RM-DPT 10004 ATEX |
|---|---|---|---|
| Measuring range | 0 ... 4000 Pa | 0 ... 5000 Pa | 0 ... 10000 Pa |
| Output signal corresponds to measuring limit |
4-20 mA ≙ 0 ... 4000 Pa |
4-20 mA ≙ 0 ... 5000 Pa |
4-20 mA ≙ 0 ... 10000 Pa |
| Full scale output (FSO) | 5000 Pa | 5000 Pa | 10000 Pa |
| Accuracy (linearity and hysteresis) |
≤ ± 1 %FSO ≙ ≤ ± 50 Pa |
≤ ± 1 %FSO ≙ ≤ ± 50 Pa |
≤ ± 1 %FSO ≙ ≤ ± 100 Pa |
| One-side overpressure safety | 140 kPa | 140 kPa | 140 kPa |
Special measuring ranges and special calibrations are possible on customer request.
| Technical specifications Device type |
Values | RM-DPT ...2 | RM-DPT ...2 ATEX | RM-DPT ...2 ...2 | RM-DPT ...2 ...2 ATEX | RM-DPT ...4 | RM-DPT ...4 ATEX |
|---|---|---|---|---|---|---|---|
| Supply voltage | 18 V ... 30 V DC | - | - | ||||
| 230 V AC or 110 V AC ± 10%, 50-60 Hz | - | - | - | - | |||
| Output signal | 4-20 mA, 2-wire connection | - | - | ||||
| 4-20 mA, 4-wire connection | - | - | - | - | |||
| Number of sensors | 1 sensor | - | - | ||||
| 2 sensors | - | - | - | - | |||
| Pressurised medium | Air and non-corrosive gases | ||||||
| Differential pressure connection | 6/4 mm hose socket | ||||||
| Response time | 10 ms | ||||||
| Burden | ≤ 300 Ω | ||||||
| Repeating accuracy | ≤ ± 0,2 % FSO | ||||||
| Ambient temperature range | -20 to +60°C | ||||||
| Humidity range of ambient air | 0 ... 95 % relative humidity of air, noncondensing | ||||||
| Altitude | Up to 3000 m above sea level | ||||||
| For explosion proof areas | ATEX approval | - | - | - |


| Product | P/N | Number or sensors |
Input voltage | Connection system |
Measuring range |
|---|---|---|---|---|---|
| RM-DPT 504 | 10600698 | 1 | 24 V DC | 4-wire connection | 0 ... 500 Pa |
| RM-DPT 1002 | 10600700 | 1 | 24 V DC | 2-wire connection | 0 ... 1000 Pa |
| RM-DPT 1004 | 10600701 | 1 | 110 V / 230 V AC | 4-wire connection | |
| RM-DPT 2002 | 10600702 | 1 | 24 V DC | 2-wire connection | 0 ... 2000 Pa |
| RM-DPT 2002 2002 | 10600703 | 2 | 24 V DC | 2-wire connection | |
| RM-DPT 2004 | 10600704 | 1 | 110 V / 230 V AC | 4-wire connection | |
| RM-DPT 4002 | 10600705 | 1 | 24 V DC | 2-wire connection | 0 ... 4000 Pa |
| RM-DPT 4002 4002 | 10600706 | 2 | 24 V DC | 2-wire connection | |
| RM-DPT 4004 | 10600707 | 1 | 110 V / 230 V AC | 4-wire connection | |
| RM-DPT 5002 | 10600708 | 1 | 24 V DC | 2-wire connection | 0 ... 5000 Pa |
| RM-DPT 5002 5002 | 10600709 | 2 | 24 V DC | 2-wire connection | |
| RM-DPT 5004 | 10600710 | 1 | 110 V / 230 V AC | 4-wire connection | |
| RM-DPT 10002 | 10600711 | 1 | 24 V DC | 2-wire connection | 0 ... 10000 Pa |
| RM-DPT 10004 | 10600713 | 1 | 110 V / 230 V AC | 4-wire connection | |
| RM-DPT 504 ATEX | 10600699 | 1 | 110 V / 230 V AC | 4-wire connection | 0 ... 500 Pa |
| RM-DPT 1002 ATEX | 10600715 | 1 | 24 V DC | 2-wire connection | 0 ... 1000 Pa |
| RM-DPT 1004 ATEX | 10600716 | 1 | 110 V / 230 V AC | 4-wire connection | |
| RM-DPT 2002 ATEX | 10600717 | 1 | 24 V DC | 2-wire connection | 0 ... 2000 Pa |
| RM-DPT 2002 2002 ATEX | 10600718 | 2 | 24 V DC | 2-wire connection | |
| RM-DPT 2004 ATEX | 10600719 | 1 | 110 V / 230 V AC | 4-wire connection | |
| RM-DPT 4002 ATEX | 10600720 | 1 | 24 V DC | 2-wire connection | 0 ... 4000 P |
| RM-DPT 4002 4002 ATEX | 10600721 | 2 | 24 V DC | 2-wire connection | |
| RM-DPT 4004 ATEX | 10600722 | 1 | 110 V / 230 V AC | 4-wire connection | |
| RM-DPT 5002 ATEX | 10600723 | 1 | 24 V DC | 2-wire connection | 0 ... 5000 Pa |
| RM-DPT 5002 5002 ATEX | 10600724 | 2 | 24 V DC | 2-wire connection | |
| RM-DPT 5004 ATEX | 10600725 | 1 | 110 V / 230 V AC | 4-wire connection | |
| RM-DPT 10002 ATEX | 10600726 | 1 | 24 V DC | 2-wire connection | 0 ... 10000 Pa |
| RM-DPT 10004 ATEX | 10600727 | 1 | 110 V / 230 V AC | 4-wire connection |
| Product | P/N | Number of sensors |
Input voltage | Connection system | Measuring range |
|---|---|---|---|---|---|
| SM 1000 DPI | 00121006 | 1 | 24 V DC | 2-wire connection | 0 ... 1000 P |
| SM 2000 DPI | 00121005 | 0 ... 2000 Pa | |||
| SM 4000 DPI | 00121008 | 0 ... 4000 Pa | |||
| SM 5000 DPI | 00121003 | 0 ... 5000 Pa | |||
| SM 10000 DPI | 00121012 | 0 ... 10000 Pa |
| Product | P/N | Number of sensors |
Input voltage | Connection system | Measuring range |
|---|---|---|---|---|---|
| SM-1000-SPST | 00121013 | 1 | Internal via the main board |
4-20 mA | 0 ... 1000 Pa |
| SM-2000-SPST | 00121011 | 4-20 mA | 0 ... 2000 Pa | ||
| SM-4000-SPST | 00121007 | 4-20 mA | 0 ... 4000 Pa | ||
| SM-5000-SPST | 00121002 | 4-20 mA | 0 ... 5000 Pa | ||
| SM-5000-SP | 00121000 | - | |||
| SM-10000-SPST | 00121009 | 4-20 mA | 0 ... 10000 Pa |